Grounding lightning to water:
A guide for using SiedarcTM
electrodes in a marine lightning grounding system
Ewen M. Thomson Ph.D.

Concepts and devices described in this document are the
property of Marine Lightning Protection and covered by existing and pending
patents.
Please enquire about licensing procedures for any
intended use.
1.
Summary
SiedarcTM electrodes are effectively lightning rods near the water and
have the same specifications as an air terminal. The electrodes supplement the grounding requirements of the typical watercraft
standard of a single 1 ft2 ground plate. They provide multiple discharge paths into the water to overcome the
fundamental problems inherent in a single, centrally-located grounding
terminal. With electrode
terminations near the waterline, lightning conductors can be routed outside sensitive areas rather than
through the middle of the vessel. In
this way a marine lightning protection system can be designed with similar conductor geometry to a land-based system. By minimizing the risk of sideflashes to
the water, an extensive bonding
system for conducting fittings is possible. The recommended layout for lightning conductors in the grounding system
comprises:
·
a loop
conductor around the perimeter of the boat at deck level
·
a network of bonding conductors at deck
level connected to the loop conductor
·
multiple external main conductors
·
internal
main conductors only where necessary
·
a grounding
terminal at the end of each main conductor.
2.1.
Components of a lightning protection system
A typical lightning protection system in a watercraft
has four major components.
1. Strike termination devices, or air
terminals, provide terminals for the lightning to attach to the watercraft.
2. Main conductors conduct the bulk of
the lightning current down towards
the water.
3. Grounding terminals allow the
current to exit into the water.
4. A
network of bonding conductors
equalizes voltages between the
lightning protection system and conducting fittings.
The grounding system provides the connecting paths between the lightning protection system and
the water. It has the following functions:
·
to initiate
current flow into the
water;
·
to establish a low impedance network for the peak lightning current;
·
to prevent
sideflashes from conducting fittings; and
·
to minimize
shock hazards for the crew.
Present standards
for lightning protection systems specify an immersed grounding terminal
with a 1 ft2 grounding area. However, grounding is more effective if multiple grounding terminals are
distributed over the hull. See http://www.thomson.ece.ufl.edu/lightning/IEEE.html Also, since current tends to flow into
the water in spark channels,
contact area can be augmented through spark initiation. See pages
4 - 6 in the April/May 2004 issue of Professional
Boatbuilder (http://www.marinelightning.com/ProBoat.pdf )
Using spark-promoting SiedarcTM electrodes
for these extra terminals, rather than immersed ground plates, has several
advantages:
·
Electrodes are designed to meet NFPA
standards for an air terminal
·
Each electrode requires only one mounting hole.
·
Electrodes can be faired into the hull, thereby reducing drag and avoiding galvanic
corrosion.
·
Electrodes are mounted preferentially above the waterline.
·
Routing lightning conductors around sensitive areas reduces emi and shock hazard.
·
Electrodes are shaped to promote initial current flow.
This Guide discusses the role and implementation of grounding
electrodes in a marine grounding system.
Its scope is to:
·
illustrate limitations in existing standards for lightning protection;
·
identify particular sideflash risks;
·
suggest layout
for lightning conductors and grounding electrodes
Yacht configurations that are appropriate for the use of this type of grounding are those
with:
·
fiberglass hulls, and
·
aluminum masts
Yacht configurations that require special consideration are those with:
·
carbon fiber hull, or
·
carbon fiber reinforcing structures in hull,
or
·
SSB ground strips embedded into hull, or
·
carbon fiber masts.
The main objectives for incorporating electrodes in the
design of the grounding system are:
·
to place electrodes near fittings that are sideflash risks;
·
to distribute
electrodes widely, preferentially along the waterline;
·
to route
connecting conductors externally to simulate a Faraday cage.
3. Improving
on traditional single-plate grounding
Recommendations for lightning protection systems are
published by several authorities,
including ABYC, NFPA, ISO ABS, and Lloyds. Generally, these specify:
·
an immersed
ground plate or strip with an area of at least 1ft2
·
a copper down conductor with a cross sectional area in the range size 21
– 58 mm2
·
bonding
of all metallic fittings close to the lightning conductor.
3.2.
Problems
There are several problems
with this scheme:
·
The
1ft2 area for a ground plate is completely inadequate in fresh water,
and even in salt water sideflashes can occur from fittings close to the water.
·
A single centrally-located down conductor maximizes the risk of generating sideflashes to other fittings and shock
hazard
·
Bonding
conducting
fittings to the lightning protection system increases the risk of a
sideflash to the water.
These problems are illustrated in the two case studies discussed in Appendix A.
3.3.
Solutions
These problems can be addressed by:
·
supplementing the 1 ft2 ground
with multiple extra grounding
terminals,
·
adding additional lightning conductors outside sensitive areas,
·
placing bonding conductors as far as possible from the water.
The main features of the grounding system are as
follows:
·
One or more main conductors are split into several grounding branches.
·
Main conductors are routed preferentially external to interior spaces.
·
Each grounding branch is terminated in a grounding terminal.
·
Multiple grounding paths maximize the discharge area around the hull.
·
Sideflash risk from a fitting to the
water is reduced in the vicinity of any grounding terminal.
·
Sideflash risk between fittings is reduced through bonding.
Steps in the procedure for designing the grounding system are
to:
·
identify regions of high sideflash risk'
·
place grounding terminals,
·
route lightning conductors.
On the basis of the cases discussed in Appendix A, we
can distinguish two types of sideflashes:
·
Internal
sideflashes connect from a fitting to another
fitting inside the
boat.
·
External
sideflashes connect to the water.
The risk of a
sideflash depends on:
·
the shape
of the conducting fitting;
·
for a fitting amidships, how close it is to
the water;
·
for a fitting near the beam, how close it is
to the waterline.
Relative risks are summarized in Table 4-1.
Fitting
|
Sideflash risk
|
Comment
|
|
Internal
|
External
|
|
CFC hull reinforcement
|
Moderate
|
Very high
|
Can destroy hull
|
|
Gel coat blister
|
Low
|
Very high
|
Also applies to water-soaked
laminate
|
|
Immersed transducer
|
Low
|
Very high
|
Can blow out
|
|
SSB foil ground on hull
|
Low
|
Very high
|
High risk to hull integrity
|
|
Chainplate
|
Low
|
High
|
Avoid current flow through
stay
|
|
Mast base
|
High if elevated
|
High
|
Aluminum mast is excellent
conductor
|
|
Tank
|
High
|
Moderate
|
Same for metal and water
tanks
|
|
Prop shaft
|
High
|
Low
|
Immersed in water
|
|
Keel bolt
|
High
|
Low
|
External sideflash through
ballast
|
|
Plumbing
|
Moderate
|
Moderate
|
Depends on location
|
|
Batteries
|
Low
|
Moderate
|
Ground connected to battery
negative
|
|
Bilge water
|
Low
|
Moderate
|
Especially if in contact with
lightning protection system
|
|
Encapsulated
ballast
|
NA
|
Moderate
|
Current flow through
ballast highly desirable
|
Table 4‑1 Relative sideflash risk for
fittings
Regions where the sideflash
risk is high are illustrated in Figure 4‑1. This is
a simplified yacht with mast,
forestay, single set of sidestays, keel bolts connecting to ballast, and a
conducting tank forward. In a more typical yacht the region of high
sideflash risk would be more
likely to encompass the complete
volume of the hull below the waterline.

Figure 4‑1
Regions of high sideflash risk
Carbon fiber
composites (CFC) present several design problems for lightning protection. Specifically,
·